OLR GENERAL USE OBSTRUCTION LIGHTING RELAY

📄 Download Datasheet: OLR-GENERAL-USE-OBSTRUCTION-LIGHTING-RELAY.pdf

OLR GENERAL USE OBSTRUCTION LIGHTING RELAY

APPLICATION:

The OLR is a universal transfer and alarm relay. It is programmable by means of a selector switch to sense up to two beacons or four obstruction light lamps. Typical applications:

SKU: olr-general-use-obstruction-lighting-relay Category: Tag:

Description

  • Lamp failure alarm relay for up to four single obstruction lights.
  • Alarm relay for one double head obstruction light with transfer of power from the failed lamp to the standby lamp.
  • Lamp failure alarm relay for up to two flashing beacons.

FEATURES/BENEFITS:

  • Solid state components for high reliability
  • Cast aluminum 4″ x 4″ x 3″ box with one-inch threaded hubs at top and bottom
  • Toroidal current sensing
  • Number of lamps selectable: 1 to 4 single head obstruction lights, 1 double head obstruction light, or 2 lamps for beacon
  • Lamp wattage selectable: 120V: 620/700W or 116W | 230V: 700W or 116W
  • Isolated alarm outputs (10 amps at 120VAC or 30VDC)
  • Spare lamp output rated 125W
  • Red LED lamp failure indicator
  • May be installed before or after a flasher unit
  • Multiple wires may be passed through the toroid such as for two beacons
  • Suitable for 50 or 60Hz frequency power
  • Voltage tolerance ±20% of 120 or 240V
  • Operating temperature: -40°F to 150°F | -40°C to 65°C